ANALISIS INTENSITAS PENCAHAYAAN DI RUANG KULIAH GEDUNG FISIKA UNIVERSITAS JEMBER DENGAN MENGGUNAKAN CALCULUX INDOOR 5.0B
Abstract: The purposes of this
research is to assess the illuminating of in classroom 35C 201 40 and 35C 210
40 phycics building University of Jember.Data retrieved by using a lux meter,
with three times the measurement at everypoint. After data was obtained from
calculation, so the data will be enteredinto Software Calculux Indoor 5.0b.
Based on the research that has been done,it showed that in classroom 35C 201 40
and 35C 210 40 not in accordancewith the standard set by Indonesian National
Standard of 250 lux, with result 79,59 lux and 77,05 lux. Whereas the result of
the measurement and calculation of the reflectances values on both the
classroom to the walls, floor, and ceiling has been corresponding of Indonesian
National Standard recommendations with a value from 0.5 until 0.8. In
accordance with thetheory of illumination for Indonesian National Standard must
full fil thecriteria: cleanliness of the room, the installation of the armature
and the light evenly, giving the bright color of the walls, floors, and
ceilings. The simulation result from Software Calculux Indoor 5.0b that is the
illuminations atclassroom 35C 201 40 better than 35C 210 40. The illumination
in bothclassroom not in accordance with the standard set by Indonesian NationalStandard,
so that it can affect of the learning process.
Penulis: Listiana Cahyantari
Kode Jurnal: jpfisikadd160422